Resumen
This study analyzed the heating and cooling performance of an office building in Daegu, Korea, equipped with amorphous-Si (a-Si) building-integrated photovoltaic (BIPV) windows. EnergyPlus was used to simulate and compare the heating and cooling loads of models for clear glass double-layer, heat-absorbing glass double-layer, and low-emissivity (low-e) glass double-layer windows. In addition, the impact of changes in building operation time, temperature settings, air infiltration from the entrances, and internal load were also analyzed as these all have a large impact on heating and cooling loads. Finally, three types of heating and cooling equipment were tested, and their power and primary energy consumption analyzed, to determine the actual energy used. Under baseline conditions, there was an 18.2% reduction in heating and cooling loads when the BIPV model was used compared to when the clear glass double-layer window was used. In addition, increases in temperature settings and air infiltration from the entrances had a negative effect on the reduction of the heating and cooling loads demonstrating a need for intensive management of these features if a-Si BIPV windows are installed in a building.