Resumen
Following the observation of severe damage to structurally isolated non-structural reinforced concrete walls after major earthquakes, researchers began to reassess the effectiveness and connection detail of non-structural walls to moment-resisting frames. A method to control damages to the non-structural wall, is to cast exterior non-structural concrete wall elements to be monolithic with frame elements, without anchoring the wall longitudinal bar. The non-anchorage of the wall longitudinal bar significantly increases the drift capacity of the wall and decreases damage. Using an experimental approach, this study assesses the influence of reinforcement detailing and quantity of the transverse reinforcements on the strength and drift capacity of the non-structural hanging wall. This study further evaluates the workability mechanism of the transverse reinforcements and reinforcement detailing with concrete. The non-anchorage of hanging walls, having boundary confinements, was found to exhibit a higher drift and strength capacity than similar walls with the anchored detailing without boundary confinements. The strength capacity of the anchored detailing hanging walls with minimum amounts of reinforcements was higher than that of the non-anchored specimen. The boundary confinements were found to be more influential on the capability of the hanging wall when placed along with non-anchored detailing reinforcement.