Resumen
The goal of this investigation is the thorough analysis and optimization of a solar-assisted heat pump heating unit for covering the space heating demand for a building in Athens, Greece. The novelty of the studied system is the use of a high-temperature heat pump that can operate with radiative terminal units, leading to high thermal comfort standards. The examined system includes flat-plate solar thermal collectors, an insulated thermal storage tank, auxiliary electrical thermal resistance in the tank and a high-temperature heat pump. The economic optimization indicates that the optimal design includes 35 m2 of solar thermal collectors connected with a storage tank of 2 m3 for facing the total heating demand of 6785 kWh. In this case, the life cycle cost was calculated at 22,694 EUR, the seasonal system coefficient of performance at 2.95 and the mean solar thermal efficiency at 31.60%. On the other hand, the multi-objective optimization indicates the optimum design is the selection of 50 m2 of solar field connected to a thermal tank of 3 m3. In this scenario, the life cycle cost was calculated at 24,084 EUR, the seasonal system coefficient of performance at 4.07 and the mean solar thermal efficiency at 25.33%.