This study presents an experimental investigation into the mechanical performance of built-up columns composed of four cold-formed square steel tubes under axial load. The four tubes were assembled together with several C-shaped connectors through two self-tapping screws in each junction. The influence of parameters including spacing between tubes, type of connectors and transverse diaphragm were analyzed based on the failure modes, ultimate loads, load-displacement relationships and load-strain relationships measured in the tests. Moreover, a further numerical analysis was carried out to study the effect of the number of connectors, web height of connectors and installing connectors at column ends by means of the verified finite element models. Finally, the numerical results were compared with the strengths predicted by the AISI-S100-2012 code. Results show that the performance of built-up columns can be influenced by the change in the number of connectors and ratio of web height of connectors to spacing between tubes as well as the installation of connectors at column ends. In addition, the current AISI-S100-12 specifications do not provide a good prediction of the built-up columns composed of four cold-formed square steel tubes.