The electrical energy impact of small-scale onsite generation: A case study of a 75 kWp grid-tied PV system

Russel Mhundwa    
Michael Simon    
Joel Nana Yongoua    

Resumen

This study presents an analysis of a 75 kWp grid-tied solar photovoltaic (PV) system with a grid tie limiter to provide energy requirements for an aquaculture centre in the Eastern Cape province of South Africa. A data acquisition system, comprising power and energy consumption meters, was deployed to measure solar PV generation, demand for the facility, and energy drawn from the utility grid. Statistical analysis was conducted on the data to determine the impact of the solar PV plant in reducing demand from the utility grid throughout the day, and this was extrapolated into monthly and annual contributions by the PV system to meeting the energy requirements. Findings reveal that the annual energy yield for the system was 1 864.29 kWh/kWp. The solar contribution to the total load requirement on a 24 hour cycle was 28% (139.82 MWh) from July 2018 to June 2019. Summer and winter average contributions by the PV system were 62% and 57% respectively for the period of 05:30?18:30. The mean monthly solar fraction for operating the farm between sunrise and sunset was 0.44. Furthermore, a total of 141.07 tCO2 has been avoided due to the operation of the PV system.