Resumen
This paper has introduced an algorithm for the identification of islanding events in the remotely located distribution grid with renewable energy (RE) sources using the voltage signals. Voltage signal is processed using Stockwell transform (ST) to compute the median-based islanding recognition factor (MIRF). The rate of change in the root mean square (RMS) voltage is computed by differentiating the RMS voltage with respect to time to compute the voltage rate of change in islanding recognition factor (VRCIRF). The proposed voltage-based islanding recognition factor (IRFV) is computed by multiplying the MIRF and VRCIRF element to element. The islanding event is discriminated from the faulty and operational events using the simple decision rules using the peak magnitude of IRFV by comparing peak magnitude of IRFV with pre-set threshold values. The proposed islanding detection method (IDM) effectively identified the islanding events in the presence of solar energy, wind energy and simultaneous presence of both wind and solar energy at a fast rate in a time period of less than 0.05 cycles compared to the voltage change rate (ROCOV) and frequency change rate (ROCOF) IDM that detects the islanding event in a time period of 0.25 to 0.5 cycles. This IDM provides a minimum non-detection zone (NDZ). This IDM efficiently discriminated the islanding events from the faulty and switching events. The proposed study is performed on an IEEE-13 bus test system interfaced with renewable energy (RE) generators in a MATLAB/Simulink environment. The performance of the proposed IDM is better compared to methods based on the use of ROCOV, ROCOF and discrete wavelet transform (DWT).