Resumen
Fault detection in heating, ventilation and air-conditioning (HVAC) systems can effectively prevent equipment damage and system energy loss, and enhance the stability and reliability of system operation. However, existing fault detection strategies have not realized high effectiveness, mainly due to the time-delay characteristics of HVAC system faults and the lack of system-fault operation data. Therefore, aiming at the time delay of system faults and the lack of actual system-fault operation data, this paper proposes a fault detection method that combines a system simulation model and an intelligent detection algorithm. The method first uses the Modelica modeling language to build a scalable simulation model of the system to obtain fault data that are not easily accessible in practice. The long short-term memory-support vector data description (LSTM-SVDD) algorithm is then applied to detect faults in real time by dynamically adjusting the fault residuals according to the absolute difference between the predicted and actual values. The experimental results show that the LSTM-SVDD method improves the average detection accuracy by 9.675% and 9.85% over the classical LSTM network and the extreme gradient boosting (XGBoost) method, respectively, under different fault levels.