Redirigiendo al acceso original de articulo en 23 segundos...
Inicio  /  Buildings  /  Vol: 12 Par: 4 (2022)  /  Artículo
ARTÍCULO
TITULO

A Simplified Thermal Comfort Calculation Method of Radiant Floor Cooling Technology for Office Buildings in Northern China

Xiaolong Wang    
Tian Mu    
Lili Zhang    
Wenke Zhang and Linhua Zhang    

Resumen

The increasing application of floor heating technology promotes the development of floor radiant cooling technology (abbreviated as FRC technology). Many office buildings in northern China try to use FRC technology to cool in summer, but thermal comfort is the key problem restricting the promotion of this technology. The thermal comfort problems of an office room with floor radiant cooling were studied in this paper by the methods of numerical simulation, control variable, and data fitting, and the experimental results were verified in multiple ways. It was found that, for an office room using floor radiant cooling, the effect of the floor surface temperature on thermal comfort was about 16%, while the effect of indoor air temperature was about 84%, and relative humidity had little effect on thermal comfort. A simplified thermal comfort calculation model was proposed, which could be used as an indicator to adjust the floor surface and indoor air temperature, or could be used to calculate the PMV-PPD value. The findings have guiding significance for the design and control of FRC technology.

 Artículos similares

       
 
Thomas Wüest, Philipp Schuetz and Andreas Luible    
The experimental setup implements a simplified PASSYS test cell construction, which is combined with a detailed simulation to reduce measurement effort. To analyze the cell?s dynamic behavior, the test cell was closely monitored with thermal sensors, and... ver más
Revista: Buildings

 
Roberta Masci and Enrico Sciubba    
Modern gas turbine firing temperatures (1500?2000 K) are well beyond the maximum allowable blade material temperatures. Continuous safe operation is made possible by cooling the HP turbine first stages, nozzle vanes and rotor blades, with a portion of th... ver más

 
Jianguang Xie, Sicheng Jia, Hua Li and Lei Gao    
Permeable pavement is often known as ?cool road?. However, the cooling performance will be weakened due to clogging. In this paper, the temperature field distribution model of asphalt pavement was obtained by Green?s function. Gradations of porous asphal... ver más
Revista: Water

 
Björn Berggren and Maria Wall    
It is important to minimize transmission heat transfer losses through the building envelope when designing and building energy efficient buildings in heating dominated climates. In such a climate, a large part of the space heating demand is caused by tra... ver más

 
Kamel Hooman, Xiaoxue Huang and Fangming Jiang    
This paper focuses on the optimization of a Solar-Enhanced Natural-Draft Dry-Cooling Tower (SENDDCT), originally designed by the Queensland Geothermal Energy Centre of Excellence (QGECE), as the air-cooled condenser of a geothermal power plant. The conve... ver más
Revista: Energies